¢º CONTACT RATINGS
Type |
SLY-2(1a1b) |
SLY-2(2a2b) |
-
|
Resistance load |
Induction load |
Resistance load |
Induction load |
Resisting load |
250VAC 15A
24VDC 15A |
250VAC 10A
24VDC 7A |
250VAC 10A
24VDC 10A |
250VAC 7.5A
24VDC 5A |
Rating sending current |
15A |
10A |
Max. contact voltage |
250VAC, 125VDC |
Max.contact current |
15A |
10A |
Max.open/close capacity |
3,750VA, 360W |
2,500VA, 168W |
2,500VA,240W |
1,875VA, 120W |
Contact materials |
AgCdO |
¢º CHARACTERISTICS
Initial contact resistance |
Below 50m§Ù |
Operating hour |
Below 20m§Ù |
Reset time |
Below 20m§Ù |
Insulation resistance |
Over 100m§Ù(at 500 V DC Meqqer) |
Intenal
voltage |
For 1 minute coil and contact
point 1,500VAC |
For 1 minute between contact
point 1,000VAC |
Vibration |
Durability |
Amplitude 1.0mm, Frequency 10-55Hz |
Misoperation |
Amplitude 1.0mm, Frequency 10-55Hz |
Impact |
Durability |
1000m/s2 (Over 100G) |
Misoperation |
200m/s2 (Over 20G) |
Life |
Electrical |
Over 200,000 times(SLY-4), Over
500,000times(SLY-2)
(Resistance Load) |
Mechanical |
Over 10,000,000 times |
Surroundig temperature |
-20¡É~ +40¡É |
Max. open/close frequence |
1,800times/hour(Resisting load)
|
Weight |
About 33g |